7) All circuits at the service equipment shall be protected by over-current
protection as required by the National Electrical Code in effect at the time
of installation. (Type C Violation)
8) Overhead conductors shall provide an 18 feet vertical clearance over all
streets, a 12 feet clearance over driveways, and a 10 feet clearance above
grade in all other areas. Electrical conductors emerging from the ground
shall be protected by enclosures or raceways for direct buried cable or to
the approved buried depth for protected conductors and up to a point 8 feet
above grade. Acceptable protection shall be rigid metal, intermediate
metal or Schedule 80 non-metallic conduit or channel. Manufactured
home power supply cords need not be enclosed in conduit or raceways.
(Type C Violation)
c) Maintenance of All Systems
All electrical systems shall be maintained in a safe condition. All damaged or
defective equipment shall be repaired or replaced, all loose equipment shall be
secured, all faceplates and panel fronts shall be in place and all live parts shall be
covered to prevent accidental contact. Tree branches that overhang distribution
wiring shall be removed. All components of the manufactured home community
electrical system shall be inspected by the manufactured home community
management and it shall be the responsibility of the licensee to have any defects
corrected. (Type C Violation)
(Source: Amended at 43 Ill. Reg. 2558, effective February 6, 2019)
Section 860.260 Fuel Supply
The distribution, storage, and use of natural gas, liquefied petroleum gas, fuel oil, or other fuels
shall be in accordance with the following:
a) The National Fire Protection Association's Installation of Oil Burning Equipment,
2016 Edition. (Type A Violation)